SECTION 05400 / 05 40 00

 

COLD-FORMED METAL FRAMING

  

 

** NOTE TO SPECIFIER **  ClarkWestern Building Systems; Metal Lath and Steel Framing Systems.
 .
 This section is based on the products of ClarkWestern Building Systems, which headquarters is located at:
 9100 Centre Pointe Drive, Suite 210
 West Chester, OH 45069
 Tel: (513) 870-1100
 Fax:  (513) 870-1300
 Email: support@clarkwestern.com
 Web: www.clarkwestern.com
 .
 ClarkWestern Building Systems has been growing to meet the continued needs of our customers and we bring with us a long and respected history in the steel framing industry.  Clark Steel Framing, located in Middletown, Ohio, has been supplying steel framing products in the eastern United States since 1981.  Clark acquired its second location Delta Metal Products in Dallas, Texas in 1999.  Since that time we have opened a plant in Jefferson, Georgia and Ocala, Florida.  In 2004, Clark Steel Framing acquired Dale Industries which added five more locations to our business.  Most recently we have announced the opening of our newest facility in Rochelle, Illinois.  In 2006, we are completing the final integration of our sister company Western Metal Lath in Riverside, California.  Western has over fifty years of experiences providing quality lath, accessories and framing products to the western United States.  The combination of Clark and Western along with our acquisition of Dale Industries and our new plant openings gives us thirteen facilities nationally..
 ClarkWestern Building Systems has grown to what we are today so we can be closer to our customers while offering them the quality products and service they have come to expect from us over the years.  We continue to expand our product lines.  We now offer industry leading shaft wall framing products and industry preferred and recognized metal corner bead products.  Our engineering division, Clark Western Design, located in Georgia and in California, is quickly becoming the industries preferred resource for light gauge framing design and consultation.  ClarkWestern Building Systems works to bring its years of experience in the industry to our customers through knowledgeable salespeople and a management team committed to the success of our customers.  We recognize that our reputation rests upon quality products competitively delivered when they are needed. What's inside those walls, not only counts it is what we build our reputation on..But, this is only the beginning; we will continue to work to be our customers preferred supplier by adding additional plants and products so that we can be the industries first choice from framing to finishing, coast to coast.
 

  •   GENERAL
    •       SECTION INCLUDES
      •          Cold-formed metal framing for:

** NOTE TO SPECIFIER **  Delete items below not required for project.

      •          Exterior load-bearing steel stud walls.
        •          Interior load-bearing steel stud walls.
        •          Exterior steel stud curtain walls.
        •          Floor joists.
        •          Roof trusses.
      •          Bridging, bracing, clips and other accessories.
    •       RELATED SECTIONS

** NOTE TO SPECIFIER **  Delete references below not relevant to this project, add others as required.

      •          Section 09110 -  Non-Load Bearing Wall Framing.
      •          Section 09205 -  Furring and Lathing: Lath and furring for interior plaster applications.
      •          Section 09210 -  Gypsum Plaster: Interior plaster applications.
      •         Section 09220 -  Portland Cement Plaster: Exterior Stucco and EIFS applications.
      •          Section 09250 -  Gypsum Board: Gypsum interior sheathing.
      •          Section 09260 -  Gypsum Board Assemblies: Shaft Walls and Area Separation Walls.
    •       REFERENCES

** NOTE TO SPECIFIER **  Delete references from the list below that are not actually required by the text of the edited section.

      •          ASTM A 780 - Standard Practice for Repair of Damaged and Uncoated Areas ofHot-Dip Galvanized Coatings.
      •          ASTM A 1003 - Standard Specification for Steel Sheet, Carbon, Metallic- and Nonmetallic-Coated for Cold-Formed Framing Members.
      •          ASTM A 653 - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the Hot-Dip Process.
      •         ASTM C 955 - Standard Specification for Load-Bearing (Transverse and Axial) Steel Studs, Runners (Tracks), and Bracing or Bridging for Screw Application of Gypsum Panel Products and Metal Plaster Bases.
      •          ASTM C 1513 - Standard Specification for Steel Tapping Screws for Cold-Formed Steel Framing Connections.
      •          ASTM C1007 - Standard Specification for Installation of Load Bearing (Transverse and Axial) Steel Studs and Related Accessories.
      •         AISI - Standard for Cold-Formed Steel Framing General Provisions.
      •          AISI -  North American Specification (NASPEC) for the Design of Cold-Formed Steel Structural Members - 2001.
      •           American Welding Society (AWS).a. AWS D1.1 "Structural Welding Code -  Steel."b. AWS D1.3 "Structural Welding Code -  Sheet Steel."
      •          AISI/COS 2001 -  Standard for Cold-Formed Steel Framing -  Prescriptive Method for One and Two Story Family Dwelling.
    •       DESIGN REQUIREMENTS
      •          Design steel in accordance with American Iron and Steel Institute Publication "Specification for the Design of Cold-Formed Steel Structural Members", except as otherwise shown or specified.
      •          Design loads: As indicated on the Structural Drawings.
      •          Design framing systems to withstand design loads without deflections greater than the following:

** NOTE TO SPECIFIER **  Delete items below not required for project.

      •         Exterior Walls: Lateral deflection of: L/240.
      •          Exterior Walls: Lateral deflection of: L/360.
      •          Exterior Walls: Lateral deflection of: L/600.
      •         Interior Load-Bearing Walls: Lateral deflection of: L/240.
      •          Interior Load-Bearing Walls: Lateral deflection of: L/360
      •           Interior Load-Bearing Walls: Lateral deflection of: L/600.
      •          Design framing systems to provide for movement of framing members without damage or overstressing, sheathing failure, connection failure, undue strain on fasteners and anchors, or other detrimental effects when subject to a maximum ambient temperature change (range) of 67 degrees C (120 degrees F).
      •          Design framing system to accommodate deflection of primary building structure and construction tolerances.
      •          Design exterior non-load-bearing curtain wall framing to accommodate lateral deflection without regard to contribution of sheathing materials.
    •       SUBMITTALS
      •          Submit under provisions of Section 01300.
      •          [ Product Data ]:  Submit manufacturer's product literature and data sheets for specified products.
      •          Manufacturers certification of product compliance with codes and standards.
      •         Shop Drawings: Submit shop drawings prepared by Clark Western Design showing:
        •          Locations of framing members, wall framing sections and opening elevations.
        •          Sizes and spacing of framing members.
        •          Methods of fastening framing members to each other and to supporting systems.
        •          Details of vertical deflection connections to structures.
        •          Locations and spacing of lateral bracing and structural bracing systems.
        •          Accessory products required for complete installation.
        •          Shop Drawings shall be signed and sealed by a registered PE (Professional cold-formed specialty Engineer) registered in the state of the project.
      •          Structural Calculations: Submit structural calculations prepared by Clark Western Design for approval.
        •          Submittal shall be signed and sealed by a registered PE (Professional cold-formed specialty Engineer) registered in the state of the project.
        •          Description of design criteria.
        •          Engineering analysis depicting stress and deflection (stiffness) requirements for each framing application.
        •          Selection of framing components, accessories, fasteners and welded connection requirements.
        •          Engineer shall have a minimum of 5 years experience with projects of similar scope.
    •       QUALITY ASSURANCE
      •          Contractor shall provide effective, full time quality control over all fabrication and erection complying with the pertinent codes and regulations of government agencies having jurisdiction.
      •          Conduct pre-installation meeting to verify project requirements, substrate conditions, and manufacturer's installation instructions.
      •          Welding Standards: Comply with applicable provisions of AWS D1.1 "Structural Welding Code-Steel" and AWS D1.3 "Structural Welding Code-Sheet Steel."
      •         Qualify welding processes and welding operators in accordance with AWS "Standard Qualification Procedure".
    •       DELIVERY, STORAGE, AND HANDLING
      •          Notify manufacturer of damaged materials received prior to installing.
      •          Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact.
      •          Store materials protected from exposure to rain, snow or other harmful weather conditions, at temperature and humidity conditions per the recommendations of ASTM C955.
  •   PRODUCTS
    •       MANUFACTURERS

** NOTE TO SPECIFIER **  The ClarkWestern Building Systems location below is that of the corporate headquarters. ClarkWestern Building Systems has manufacturing locations throughout the United States.

      •          Acceptable Manufacturer:  ClarkWestern Building Systems, which is located at: 9100 Centre Pointe Drive, Suite 210; West Chester, OH 45069; Tel: (513) 870-1100; Fax: (513) 870-1300; Email: support@clarkwestern.com; Web: www.clarkwestern.com
      •          Requests for substitutions will be considered in accordance with provisions of Section 01600.
      •          All products to be manufactured by current members of theSteel Stud Manufacturers Association (SSMA).
    •       COMPONENTS

** NOTE TO SPECIFIER **  Select from the following product criteria as required for the project requirements. Delete product sections below not required for project.

      •          Structural Studs: Cold-Formed galvanized steel C-studs.

** NOTE TO SPECIFIER **  Select FLANGE LENGTH. Delete Four of the next five paragraphs.  If more than one size is required, identify the location where each product will be used on the Contract Drawings.  162 inch flange is the most common size.

        •          Flange Length: 1 5/8 inch (41mm) 162 flange.
        •          Flange Length: 2 inch (51mm) 200 flange.
        •          Flange Length: 2 1/2 inch (64mm) 250 flange.
        •          Flange Length: 3 inch (76 mm) 300 flange.
        •          Flange Length: 3 1/2 inch (88.9 mm) 350 flange.

** NOTE TO SPECIFIER **  Select required WEB or WALL DEPTH. 15 of the next 16 paragraphs.  If more than one size is required, identify the location where each product will be used on the Contract Drawings.  250, 350 depths available only with 162 Flange. 362 to 925 depths available only up to 250 Flange.

        •          Web Depth: 2 1/2 inch (64 mm) 250 depth.
        •          Web Depth: 3 1/2 inch (89 mm) 350 depth.
        •          Web Depth: 3 5/8 inch (92 mm) 362 depth.
        •          Web Depth: 4 inch (102 mm) 400 depth.
        •        Web Depth: 5 1/2 inch (140 mm) 550 depth.
        •        Web Depth: 6 inch (152.4 mm) 600 depth.
        •        Web Depth: 7 1/4 inch (184 mm) 725 depth.
        •        Web Depth: 8 inch (203 mm) 800 depth.
        •        Web Depth: 9 1/4 inch (235 mm) 925 depth.
        •        Web Depth: 10 inch (254 mm) 1000 depth.
        •        Web Depth: 11 1/2 inch (292 mm) 1150 depth.
        •        Web Depth: 12 inch (305 mm) 1200 depth.
        •        Web Depth: 13 1/2 inch (342.9 mm) 1350 depth.
        •        Web Depth: 14 inch (355.6 mm) 1400 depth.
        •        Web Depth: 16 inch (406.4 mm) 1600 depth.
        •        Web Depth: As indicated on drawings.

** NOTE TO SPECIFIER **  Select MINIMUM MATERAL THICKNESS. Delete seven of the next eight paragraphs.  If more than one thickness is required, identify the location where each product will be used on the Contract Drawings.  33 mil not available with 10 or 12 inch (1000 or 1200) web.  43 mil not available with 12 inch (1200) web.

        •        Minimum Material Thickness: 33 mil (20 gauge) -  ASTM color reference: white.
          •          Design Thickness: 0.0346 in. (0.88 mm).
          •          Minimum Delivered Thickness: 0.0329 in. (0.84 mm).
        •        Minimum Material Thickness: 43 mil (18 gauge) -  ASTM color reference: yellow.
          •          Design Thickness: 0.0451 in. (1.14 mm).
          •          Minimum Delivered Thickness: 0.0428 in. (1.09 mm).
        •        Minimum Material Thickness: 54 mil (16 gauge) -  ASTM color reference: green.
          •          Design Thickness: 0.0566 in. (1.44 mm).
          •          Minimum Delivered Thickness: 0.0538 in. (1.37 mm).
        •        Minimum Material Thickness: 68 mil (14 gauge) - ASTM color reference: orange.
          •          Design Thickness: 0.0713 in. (1.81 mm).
          •          Minimum Delivered Thickness: 0.0677 in. (1.72 mm).
        •        Minimum Material Thickness: 97 mil (12 gauge) -  ASTM color reference: red.
          •          Design Thickness: 0.1017 in. (2.58 mm).
          •          Minimum Delivered Thickness: 0.0966 in. (2.45 mm).
        •        Minimum Material Thickness: 118 mil (10 gauge) -  ASTM color reference: blue.
          •          Design Thickness: 0.1242 in. (3.15 mm).
          •          Minimum Delivered Thickness: 0.1180 in. (3.00 mm).
        •        Minimum Material Thickness: As required by design.
        •        Minimum Material Thickness: As indicated on drawings.

** NOTE TO SPECIFIER **  Select MINIMUM YIELD STRENGTH. Delete two of the next three paragraphs.  33ksi material is provided if not ordered otherwise.

        •        Minimum Yield Strength: 33ksi (227 MPa) (for 33mils through 118mils).
        •        Minimum Yield Strength: 50ksi (345 MPa) (optional for 54mils and up).
        •        Minimum Yield Strength: As required by design.
      •          Structural Track: Cold-Formed galvanized steel runner tracks

** NOTE TO SPECIFIER **  Select FLANGE DEPTH. Delete five of the next six paragraphs. If more than one size is required, identify the location where each product will be used on the Contract Drawings. T125 flange is the most  common flange size.

        •          Flange Length: 1 1/4 inch (32 mm) T125 flange.
        •          Flange Length: 1 1/2 inch (38 mm) T150 flange.
        •          Flange Length: 2 inch (51 mm) T200 flange.
        •          Flange Length: 2 1/2 inch (63 mm) T250 flange.
        •          Flange Length: 3 inch (76mm) T300 flange.
        •          Flange Length: 3 1/2 inch (89 mm) T350 flange.

** NOTE TO SPECIFIER **  Select required WEB or WALL DEPTH.  Delete 15 of the next 16 paragraphs.  If more than one size is required, identify the location where each product will be used on the Contract Drawings.

        •          Web: 2 1/2 inch (64mm) 250 depth.
        •          Web: 3 1/2 inch (89mm) 350 depth.
        •          Web: 3 5/8 inch (92mm) 362 depth.
        •        Web: 4 inch (102mm) 400 depth.
        •        Web: 5 1/2 inch (140mm) 550 depth.
        •        Web: 6 inch (152.4mm) 600 depth.
        •        Web: 7 1/4 inch (184 mm) 725 depth.
        •        Web: 8 inch (203mm) 800 depth.
        •        Web: 9 1/4 (235 mm) 925 depth.
        •        Web: 10 inch (254mm) 1000 depth.
        •        Web: 11 1/2 inch (292 mm) 1150 depth.
        •        Web: 12 inch (305mm) 1200 depth.
        •        Web: 13 1/2 inch (342.9 mm) 1350 depth.
        •        Web: 14 inch (355.6 mm) 1400 depth.
        •        Web: 16 inch (406.4 mm) 1600 depth.
        •        Web: Track Web Size to match stud web size.

** NOTE TO SPECIFIER **  Select MINIMUM MATERAL THICKNESS. Delete eight of the next nine paragraphs.  If more than one thickness is required, identify the location where each product will be used on the Contract Drawings.  33 mil not available with 10 or 12 inch (1000 or 1200) web.  43 mil not available with 12 inch (1200) web.

        •        Minimum Material Thickness: 33 mil (20 gauge) -  ASTM color reference: white.
          •          Design Thickness: 0.0346 in. (0.88 mm).
          •          Minimum Delivered Thickness: 0.0329 in. (0.84 mm).
        •        Minimum Material Thickness: 43 mil (18 gauge) -  ASTM color reference: yellow.
          •          Design Thickness: 0.0451 in. (1.14 mm).
          •          Minimum Delivered Thickness: 0.0428 in. (1.09 mm).
        •        Minimum Material Thickness: 54 mil (16 gauge) -  ASTM color reference: green.
          •          Design Thickness: 0.0566 in. (1.44 mm).
          •          Minimum Delivered Thickness: 0.0538 in. (1.37 mm).
        •        Minimum Material Thickness: 68 mil (14 gauge) - ASTM color reference: orange.
          •          Design Thickness: 0.0713 in. (1.81 mm).
          •          Minimum Delivered Thickness: 0.0677 in. (1.72 mm).
        •        Minimum Material Thickness: 97 mil (12 gauge) -  ASTM color reference: red.
          •          Design Thickness: 0.1017 in. (2.58 mm).
          •          Minimum Delivered Thickness: 0.0966 in. (2.45 mm).
        •        Minimum Material Thickness: 118 mil (10 gauge) -  ASTM color reference: blue.
          •          Design Thickness: 0.1242 in. (3.15 mm).
          •          Minimum Delivered Thickness: 0.1180 in. (3.00 mm).
        •        Minimum Material Thickness: As required by design.
        •        Minimum Material Thickness: As indicated on drawings.
        •        Minimum Material Thickness: Track Thickness to match wall stud thickness.

** NOTE TO SPECIFIER **  Select MINIMUM YIELD STRENGTH. Delete two of the next three paragraphs.  33ksi is typically used for track.

        •        Minimum Yield Strength: 33ksi (227 MPa) (for 33mils through 118mils).
        •        Minimum Yield Strength: 50ksi (345 MPa) (optional for 54mils and up).
        •        Minimum Yield Strength: As required by design.
      •          Deflection Track: Cold-Formed Deep Leg Runner Slip Track.

** NOTE TO SPECIFIER **  Select Deflection Track LEG LENGTH. Delete four of the next five paragraphs.  If more than one thickness is required, identify the location where each product will be used on the Contract Drawings.
 - 250 Flange is required for a 3/4" deflection gap.
 - 300 Flange is required for a 1" deflection gap.

        •          Leg Length: 2 inch (51 mm) T200 flange.
        •          Leg Length: 2 1/2 inch (63 mm) T250 flange.
        •          Leg Length: 3 inch (76mm) T300 flange.
        •          Leg Length: 3 1/2 inch (89 mm) T350 flange.
        •          Leg Length: As required by design.

** NOTE TO SPECIFIER **  Select Deflection Track THICKNESS.  Delete six of the next seven paragraphs.  If more than one thickness is required, identify the location where each product will be used on the Contract Drawings.

        •          Minimum Material Thickness: 33 mil (20 gauge).
        •          Minimum Material Thickness: 43 mil (18 gauge).
        •          Minimum Material Thickness: 54 mil (16 gauge).
        •          Minimum Material Thickness: 68 mil (14 gauge).
        •        Minimum Material Thickness: 97 mil (12 gauge).
        •        Minimum Material Thickness: 118 mil (10 gauge).
        •        Minimum Material Thickness: As required by design.

** NOTE TO SPECIFIER **  Select MINIMUM YIELD STRENGTH. Delete two of the next three paragraphs.

        •        Minimum Yield Strength: 33ksi (227 MPa) (for 33mils through 118mils).
        •        Minimum Yield Strength: 50ksi (345 MPa) (optional for 54mils and up).
        •        Minimum Yield Strength: As required by design.
      •         Deflection Clips:

** NOTE TO SPECIFIER **  Select Deflection Clip.  Delete three of the next four paragraphs.  If more than one clip is required, identify the location where each product will be used on the Contract Drawings.

        •          Clark Slide Clip: Minimum Thickness: 68mils (14ga) 0.0677" (50ksi).
        •          Clark Channel Slide Clip: Minimum Thickness: 68mils (14ga) 0.0677" (50ksi).
        •          Clark Channel Slide Clip: Minimum Thickness: 97mils (12ga) 0.0966" (50ksi).
        •          Slide Clips: As required by design.
      •          Standard Clip Angels:

** NOTE TO SPECIFIER **  Select Standard Clip Angels.  Delete three of the next four paragraphs.  If more than one clip is required, identify the location where each product will be used on the Contract Drawings.

        •          Clip Angels: Minimum Thickness: 54mils (16ga) 0.0538" (50ksi).
        •          Clip Angels: Minimum Thickness: 68mils (14ga) 0.0677" (50ksi).
        •          Clip Angels: Minimum Thickness: 97mils (12ga) 0.0966" (50ksi).
        •          Clip Angels: As required by design.
      •          SwiftClip Support Clips: Clark Western's Pre-punched support clips.

** NOTE TO SPECIFIER **  Select SwiftClip Profiles required in this project.  Delete others not required.

        •          SwiftClip L-Series: 1-1/2" Leg x 1-1/2" Leg, length and thickness per design.
        •          SwiftClip L-Series: 1-1/2" Leg x 3" Leg, length and thickness per design.
        •          SwiftClip L-Series: 3" Leg x 3" Leg, length and thickness per design.
        •          SwiftClip L-Series: As required by design.
      •         U-Channel (CRC Cold Rolled Channel):

** NOTE TO SPECIFIER **  Select U-Channel Size required in this project.  Delete others not required.

        •          Size: 150U50-54 1-1/2" (38mm) 54mils (16ga.).
        •          Size: 075U50-54 3/4" (19.1mm) 54mils (16ga.).
        •          Size: As required by design.
      •          Furring Channel: Furring existing walls and suspended ceiling applications.

** NOTE TO SPECIFIER **  Select Furring Channel required in this project.  Delete others not required.

        •          Size: 087F125-33 7/8" (22mm) Furring Channel 33mils (20ga).
        •          Size: 087F125-43 7/8" (22mm) Furring Channel 43mils (18ga).
        •          Size: 087F125-54 7/8" (22mm) Furring Channel 54mils (16ga).
        •          Size: 150F125-33 1-1/2" (38mm) Furring Channel 33mils (20ga).
        •          Size: 150F125-43 1-1/2" (38mm) Furring Channel 43mils (18ga).
        •          Size: 150F125-54 1-1/2" (38mm) Furring Channel 54mils (16ga).
        •          Size: As required by design.
      •           Framing Accessories: Accessories required in this project.

** NOTE TO SPECIFIER **  Select Accessories required in this project.  Delete others not required.

        •          Flat Strapping for X-Bracing.
        •          Flat Strapping and bridging for lateral bracing.
        •          Gusset Plates.
      •          Fasteners: Self-drilling, self-tapping screws; complying with ASTM C 1513 - Standard Specification for Steel Tapping Screws for Cold-Formed Steel Framing Connections.
      •          Touch-Up Paint: Complying with ASTM A 780 - Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings.
    •       MATERIALS
      •          Steel: Galvanized Steel meeting or exceeding the requirements of ASTM A 1003.

** NOTE TO SPECIFIER **  Select GALVANIZED COATING.- G60 is the most common coating for structural systems.
 - G90 is use if additional protective coating is required for the project.- G90 is a special order product and should be specified in severely corrosive environments.

        •          Coating: Galvanized G60 coating minimum, complying with ASTM C 955.
        •          Coating: Galvanized G90 coating minimum, complying with ASTM C 955.
      •          Stud Punch Outs: 12 inches (305mm) from base and every 24 inches (610mm) thereafter.
  •   EXECUTION
    •       INSPECTION
      •          Inspect supporting substrates and structures for compliance of proper conditions for installation and performance of the cold-formed structural framing.
    •       PREPARATION
      •          Prepare attachment surfaces so that they are plumb, level, and in proper alignment for accepting the clod-formed structural framing.
    •       FABRICATION
      •          Prior to fabrication of framing, submit shop drawings to the architect or engineer to obtain approval.
      •          Framing components may be preassembled into panels prior to erecting.  Prefabricate panels so they are square, with components attached in a manner which prevents racking and minimizes distortion during lifting and transport.
      •          Cut all framing components square for attachment to perpendicular members or as required for an angular fit against abutting members.
      •         Plumb, align and securely attach studs to flanges of both upper and lower runners, except that in the case of interior, non-load bearing walls where studs need not be attached to upper or lower runners.
      •          In all doubled jamb studs and doubled headers not accessible to insulation contractors, provide insulation equal to that specified elsewhere.
      •          Splices in members other than top and bottom runner track are not permitted.
      •         Provide temporary bracing where required, until erection is complete.
    •       INSTALLATION -  NON-AXIAL LOAD-BEARING CURTAIN WALLS
      •          Runners shall be securely anchored to the supporting structure as shown on the drawings.
      •          Jack studs or cripples shall be installed below window sills, above window and door heads, and elsewhere to furnish supports.
      •          Lateral bracing shall be provided by use of gypsum board and gypsum sheathing or by horizontal straps or cold-rolled channels. Bracing shall conform to Section D3 of the AISI North American Specification (NAS).
      •         Provisions for structure vertical movement shall be provided where indicated on the drawings prepared by the engineer of record.
      •          Handling and lifting of prefabricated panels shall be done in a manner so as not to cause distortion in any member.
    •       INSTALLATION - AXIAL LOAD-BEARING WALLS
      •          Securely anchor runners to the supporting structure as shown on the drawings.
      •          Provide complete, uniform and level bearing support at the bottom runner.
      •          Include headers and supporting studs at wall openings as shown on the drawings.
      •         Provide diagonally braced stud walls, as indicated on the drawings at locations designated as "shear walls" for frame stability and lateral load resistance.  Position additional studs when necessary or as indicated on the drawings to resist the vertical components.
      •          Splices in axially loaded studs are not permitted.
    •       INSTALLATION - JOISTS
      •          Align joist bearing at foundation walls by means of shims and/or non-setting grout.
      •          Locate joists or a load distribution member directly over bearing studs at the top of bearing walls.
      •          Provide web stiffeners at reaction points and/or points of concentrated loads or where indicated on the drawings.
      •         Install joist bridging where indicated on the drawings.
      •          Install additional joists under parallel partitions when the partition length exceeds one-half the joist span, also around all floor and roof openings, which interrupt one or more spanning members unless otherwise noted.
      •          Install end blocking where joist ends are not otherwise restrained from rotation.
    •       INSTALLATION - TRUSSES
      •          Install trusses in accordance with applicable building code requirements and the truss manufacturer's recommendations.
      •          Refer to AISI RG-9518 for additional information.
      •          Install roof bracing in accordance with the truss design.
      •         Install trusses with the plane of the truss webs plumb and parallel to each other, aligned and accurately positioned.
        •          Truss Spacing: 16 inches (406 mm) on center.
        •          Truss Spacing: 24 inches (610 mm) on center.
        •          Truss Spacing: As required by design.
      •          Install each truss directly over a bearing stud or a load distribution member designed for this purpose.
      •          Install lateral supports as required per manufacturer's design.
      •         Immediately after installation, install bridging and permanently brace trusses per truss design.
      •          Install approved uplift connectors to connect individual truss to wall studs as required by design.

 

END OF SECTION